BS 6622 Three Core Armoured 6.6kV XLPE Stranded Copper Conductors
Construction
cross-sectional area mmsq  | 
    Minimum average thickness of insulation mm  | 
    Nominal area of copper tape screen mmsq  | 
    Nominal thickness of PVC bedding 
  | 
    Nominal number and diameter of armoured wires no./ mm  | 
    Nominal thickness of PVC oversheath mm  | 
    Nominal overall diameter of cable mm  | 
  
50  | 
    2.5  | 
    15.0  | 
    1.3  | 
    45/2.5  | 
    2.5  | 
    48.4  | 
  
70  | 
    2.5  | 
    16.8  | 
    1.3  | 
    49/2.5  | 
    2.6  | 
    52.4  | 
  
95  | 
    2.5  | 
    18.5  | 
    1.4  | 
    54/2.5  | 
    2.7  | 
    56.5  | 
  
120  | 
    2.5  | 
    20.0  | 
    1.5  | 
    57/2.5  | 
    2.8  | 
    60.1  | 
  
150  | 
    2.5  | 
    21.3  | 
    1.5  | 
    60/2.5  | 
    2.9  | 
    63.1  | 
  
185  | 
    2.5  | 
    23.1  | 
    1.6  | 
    65/2.5  | 
    3  | 
    67.4  | 
  
240  | 
    2.6  | 
    25.5  | 
    1.7  | 
    71/2.5  | 
    3.2  | 
    73.2  | 
  
300  | 
    2.8  | 
    28.3  | 
    1.8  | 
    62/3.15  | 
    3.5  | 
    81.3  | 
  
400  | 
    3.0  | 
    31.4  | 
    2.0  | 
    69/3.15  | 
    3.7  | 
    88.8  | 
  
Installation
cross-sectional area mmsq  | 
    Approximate cable weight kg/m  | 
    Nominal drum length   | 
    Minimum bending radius mm  | 
    Nominal internal diameter of ducts mm  | 
  
50  | 
    4.9  | 
    750  | 
    600  | 
    100  | 
  
70  | 
    5.8  | 
    750  | 
    650  | 
    100  | 
  
95  | 
    6.9  | 
    500  | 
    700  | 
    100  | 
  
120  | 
    7.9  | 
    500  | 
    750  | 
    100  | 
  
150  | 
    8.9  | 
    500  | 
    800  | 
    125  | 
  
185  | 
    10.4  | 
    450  | 
    850  | 
    125  | 
  
240  | 
    12.7  | 
    400  | 
    900  | 
    125  | 
  
300  | 
    16.0  | 
    400  | 
    1000  | 
    125  | 
  
400  | 
    19.4  | 
    350  | 
    1100  | 
    -  | 
  
Electrical Performance
cross-sectional area mmsq  | 
    Maximum DC resistance of conductor at 20 ¡æ uohms/m  | 
    Maximum AC resistance of conductor at 90 ¡æ uohms/m  | 
    Reactance at 50Hz   | 
    Impedance at 50Hz uohms/m  | 
    Maximum Capacitace PF/m  | 
    Maximum charging current at normal voltage and frequency mA/m  | 
  
50  | 
    387  | 
    494  | 
    108  | 
    506  | 
    332  | 
    0.40  | 
  
70  | 
    268  | 
    343  | 
    102  | 
    358  | 
    383  | 
    0.46  | 
  
95  | 
    193  | 
    248  | 
    96.2  | 
    266  | 
    432  | 
    0.52  | 
  
120  | 
    153  | 
    196  | 
    93.1  | 
    217  | 
    474  | 
    0.57  | 
  
150  | 
    124  | 
    159  | 
    90.8  | 
    183  | 
    511  | 
    0.61  | 
  
185  | 
    99.1  | 
    128  | 
    88.1  | 
    155  | 
    562  | 
    0.67  | 
  
240  | 
    75.4  | 
    98  | 
    85.9  | 
    130  | 
    602  | 
    0.72  | 
  
300  | 
    60.1  | 
    80  | 
    84.7  | 
    117  | 
    622  | 
    0.75  | 
  
400  | 
    47.0  | 
    64  | 
    83.2  | 
    105  | 
    648  | 
    0.78  | 
  
Ratings
Cross-sectional area   | 
    Current Ratings  | 
    Short circuit ratings  | 
  |||
Laid direct in ground   | 
    Drawn into ducts   | 
    Laid in air   | 
    One second short circuit rating of conductor   | 
    One second short circuit rating of copper per core   | 
  |
50  | 
    210  | 
    180  | 
    220  | 
    6.8  | 
    Typically  
  | 
  
70  | 
    255  | 
    215  | 
    270  | 
    9.8  | 
  |
95  | 
    300  | 
    255  | 
    330  | 
    13.3  | 
  |
120  | 
    340  | 
    290  | 
    375  | 
    17.2  | 
  |
150  | 
    380  | 
    330  | 
    430  | 
    21.2  | 
  |
185  | 
    430  | 
    370  | 
    490  | 
    26.6  | 
  |
240  | 
    490  | 
    425  | 
    570  | 
    34.9  | 
  |
300  | 
    540  | 
    470  | 
    650  | 
    43.8  | 
  |
400  | 
    590  | 
    520  | 
    700  | 
    57.3  | 
  |
website: www.caledonian-cables.com